Technical requirements for high voltage switchgear

Oct 03, 2026 Leave a message

1. The manufacture, testing, and installation of the high-voltage switchgear shall meet the relevant current standards of the People's Republic of China and the relevant requirements of the Beijing Power Supply Bureau.

 

2. Main technical parameters: Rated voltage 12KV; Rated current 630A; Rated short-circuit breaking current 25KA; Rated frequency 50HZ; Rated peak making current 63KA; Rated short-circuit withstand current 25KA/4S; AC 220V operation.

 

3. Main equipment inside the cabinet: Circuit breaker VD4-12/630-25; High-voltage fuse XRNP1-12/1A; Relay protection RCR313B microcomputer protection device; Current transformer LZZBJ9-10AC; Voltage transformer JDZ18-10Q; Surge arrester HY5WZ2-17/43.5; Grounding switch JN15-12/31.5-210; Live indicator GXNE-12.

 

4. High-voltage switchgear structure and composition: The switchgear is manufactured using imported aluminum-zinc coated steel plates. The cabinet is an indoor metal-armored removable structure, wall-mounted. The switchgear meets five protection requirements, with an IP40 protection rating. The switchgear dimensions do not exceed: 800mm x 1350mm x 2200mm (width x depth x height), with bottom-in and bottom-out cabling.

 

5. Foundation civil engineering modifications for the distribution cabinet.

 

6. Power outage time: to be reported by the bidding unit.