Typical Load Of AC Contactor

Sep 19, 2026 Leave a message

(1) Heating element load: The current of a wire-wound resistor element can reach 1.4 times its rated value after being energized (e.g., heating/air conditioning equipment). A 10% increase in grid voltage will lead to a significant increase in current, requiring thorough analysis to select the appropriate contactor rated current.

(2) Lighting devices: Incandescent lamps experience an inrush current of 15 times their rated current when switched on, and the current increases dramatically with a 10% increase in voltage, classifying them as AC-5b. Other lighting fixtures are classified as AC-5a due to their inrush current value, starting time, and power factor ≠ 1.

(3) Low-voltage transformer load: The peak current reaches 15-20 times its rated value when switched on (related to winding and core characteristics). For example, during a short circuit operation on the secondary side of a welding machine transformer, the primary side switch bears strong current stress.

(4) Capacitor load: The transient charging current is extremely high upon switching on, accompanied by high-frequency oscillations, placing stringent requirements on electrical switches.

(5) Motor load: Wound-rotor motors belong to AC-2 category (rotor circuit resistance limits current, and starting time is extended as the load increases); squirrel-cage motors have an effective value of 4 to 8 times the impact current when starting directly, and the current becomes steady-state after decay.